10ka miniature circuit breaker 1p 2p 3p 4p main switch MCB

 Standard IEC/EN 60898-1IEC/EN 60947-2Electrical featuresRated current InA1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63Poles  1P, 1P+N, 2P, 3P, 3P+N, 4P1P, 2P, 3P, 4PRated voltage UeV230/400~240/415Insulation voltage UiV500Rated frequency  50/60HzRated breaking capacityA60006000Energy

Featured Products

 Standard IEC/EN 60898-1IEC/EN 60947-2
Electrical featuresRated current InA1, 2, 3, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50, 63
Poles  1P, 1P+N, 2P, 3P, 3P+N, 4P1P, 2P, 3P, 4P
Rated voltage UeV230/400~240/415
Insulation voltage UiV500
Rated frequency  50/60Hz
Rated breaking capacityA60006000
Energy limiting class   
Rated impulse withstand voltage(1.2/50) UimpV4000
Dielectric test voltage at ind. Freq. For 1 minKV21.890
Pollution degree  2
Power loss per pole  Rated current (A)Max power loss per pole (W) 
 1, 2, 3, 4, 6, 10
 16, 20, 25, 323.5 
 40, 50, 635
Thermo-magnetic release characteristic  B, C, D(8-12)In
Mechanical featuresElectrical life  4000
Mechanical lif  20000
Contact position indicator  YES
Protection degree  IP20
Reference temperature for setting of thermal element ºC30
Ambient temperature (with
Daily average≤35ºC)
ºC-5...+40
Storage temperationºC-25...+70
InstallationTerminal connection type  Cable/U-type busbar/Pin-type busbar
Terminal size top/bottom for cablemm225
AWG18-4
Terminal size top/bottom for busbarmm210
AWG18-8
Tightening torqueN·m2.5
In-Ibs. 22
Mounting  On DIN rail EN 60715 (35mm) by means of fast clip device
Connection  From top and bottom
Combination with accessoriesAuxiliary contact  YES
Shunt release  YES
Under voltage release  YES
Alarm contant  YES
    1. Selectivity







Load side: K NB1-63, KNB1-63H
Curve B, C
In (A)Power supply side: RT36-00 (fuse)
202536506380100125160
Is (kA)
≤21.24>12>12>12>12>12>12>12
30.71.23.85.366666
40.60.92.53.866666
60.50.81.92.54.55666
10  0.71.42.23.23.6666
16    1.21.82.635.666
20      1.52.22.54.666
25      1.322.24.15.56
32        1.71.93.84.56
40          1.7345
50          1.52.63.54.5
63            2.43.34.5




Load side: KNB1-63, KNB1-63H
Curve B, C
In (A)Power supply side: NM8-100S/H/R
1620253240506380100
Is (kA)
≤100.190.190.30.40.50.50.50.630.8
16    0.30.40.50.50.50.630.8
20        0.50.50.50.630.8
25          0.50.50.630.8
32            0.50.630.8
40              0.630.8
50                0.8
63                  
    1. Backup protection






Load side: K NB1-63, KNB1-63H
Curve B, C
In (A)Power supply side: RT16 series
40506380100125160
Is (kA)
1~640404040404040
8~1040404040404040
1340404040353535
1640404040303030
2040404040303030
2540404040303030
3240404040303030
4040404040303030
5030303030303030
6320202020151515


Load side: KNB1-63, KNB1-63H
Curve B, C
In (A)Power supply side: NM8
NM8-125SNM8-125HNM8-125RNM8-250SNM8-250HNM8-250R
Is (kA)
1~6151818151515
10~20121515121212
32~40121515121212
50~60121515121212
 
    1. Temperature derating
The maximum permissible current in a circuit breaker depends on the ambient temperature where the circuit breaker is
Placed. Ambient temperature is the temperature inside the enclosure or switchboard in which the circuit breakers are installed. 

The reference temperature is 30ºC

Ambient temperature                         
 -35ºC-30ºC-20ºC-10ºC0ºC10ºC20ºC30ºC40ºC50ºC60ºC70ºC
Rated current(A)                        
11.301.261.231.191.151.111.051.000.960.930.880.83
22.602.522.462.382.282.202.082.001.921.861.761.66
33.903.783.693.573.423.303.123.002.882.792.642.49
45.205.044.924.764.564.404.164.003.843.763.523.32
67.807.567.387.146.846.606.246.005.765.645.284.98
1013.2012.7012.5012.0011.5011.1010.6010.009.609.308.908.40
1621.1220.4820.0019.2018.4017.7616.9616.0015.3614.8814.2413.44
2026.4025.6025.0024.0023.0022.2021.2020.0019.2018.6017.8016.8
2533.0032.0031.2530.0028.7527.7526.5025.0024.0023.2522.2521.00
3242.5641.2840.0038.7237.1235.5233.9232.0030.7229.7628.1626.88
4053.2051.2050.0048.0046.4044.8042.4040.0038.4037.2035.6033.6
5067.0065.5063.0060.5058.0056.0053.0050.0048.0046.5044.0041.50
6383.7981.9080.0176.8673.7170.5666.7863.0060.4858.9055.4452.29


When several simultaneously operating circuit breakers are mounted side by side in a small enclosure, the temperature rise inside the enclosure causes a reduction in current rating. 
You must then assign the rating (already derated if necessary according to ambient temperatuer) a downrating factor of 0.8. 
10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB

Company Introduction

10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB


Wenzhou Korlen Electric Appliances Co., Ltd, It is a joint venture. My company is a manufacturer including design, development, produce and sale, professional producing MCB, MCCB, RCCB and AC contactor etc. Product enterprises. The company owns import and export power of self-run, expanding Europe and America, Middle East, Southeast Asia etc. Market, set a good Public praise.

The company have more than 1500 workers, including senior engineer among them, engineer at inside of more than 100 technician. And then set up to cover area more than 50 acres, construct area is more than 38000 square meters of the modern industrial zone, providing with the forerunner's standard laboratory and various examination equipments.

Under Korlen people to make great effort unremittingly, designed and developed by oneself, develop and produce the series of MCB, RCCB filled up local blank, attain inter-national advanced level, and acquire more than 20 national patents. The company acquires "30 strong eminent enterprises, top ten of export income, yueqing star class enterprise, attach importance to contract and keeps promise" title of honor for many times past years. Company still the initiative pass ISO 9001 management system verification and 14001 environments management system verification. Our product passed quality verification of domestic and international authority organization like the CB\ SEMKO\ NF\ SIRIM\ SNI\ CE \PCT\ TSE, In the meantime high breaking capacity breaker of our company in this city is the unique product which got " Yueqing famous brand product" by Yueqing people government.

Korlen Electric Appliances is willing to make friends with social public, the world outside businessman join hands together for prosperous society and development to build a brighter future.



Certificates

10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB

Factory Lines

10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB
10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB

Exhibition

10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB
10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB


10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB10ka Miniature Circuit Breaker 1p 2p 3p 4p Main Switch MCB


 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours