NS series CE MCCB NS series moulded case circuit breaker/mccb is one of the most advanced type breakers in the world, which adopt international advanced design and manufacture fechnology. They are suitable for short circuit and overload protection for circuit of AC 690V 50/60Hz, rated current from 12.5A to 630A.

Featured Products


NS series CE MCCB
 
NS series moulded case circuit breaker/mccb is one of the most advanced type breakers in the world, which adopt international advanced design and manufacture fechnology. They are suitable for short circuit and overload protection for circuit of AC 690V 50/60Hz, rated current from 12.5A to 630A. It takes protect effect when mouse cage motors non-frequent start, breaking off working and protecting overload, short circuit and lacking voltage. 

Tripping Characteristics of MCCB 
Rated Current of Release(A) Thermodynamic Release (ambient temp +40C) Operational Current of Magnetic Release(A) 
1.05In(cold state) inoperative time(h) 1.30In(heat state) operative time(h) 
In≤ 63 ≥ 1 <1 10In+20% 
63 ≥ 2 <2 10In +20% 
100 ≥ 2 <2 5-10In+20% 

Rated Current of Release(A) Thermodynamic Release (ambient temp +40C) Operational Current of 
Magnetic 
Release(A) 
1.0In(cold state)operative time(h) 1.20In(heat state)operative time(h) 1.50In(heat state)operative time(h) 1.01In(heat state)operative time(h) 
12.5≤ In≤ 400 ≥ 2 <2 ≤ 4min S 12In+20% 

Main Technical Specifications 
Type Rated Current (A) Poles Rated Insulating Voltage(A) Rated Operating Voltage (A) Acting Over Distance (mm) Ultimate short circuit Breaker Capacity Servies Short Circuit Breaker Capacity Operating performance(times)

Rated current of release(A)
Thermodynamic release(ambient temp+40 )Operation current of magnetic release(A)
1.05ln(cold state)
inoperative time(h)
1.30ln(heat state)
inoperative time(h)
ln 631110ln 20%
63 ln 1002210ln 20%
100 ln 630225-10ln 20%
 
Rated current of release(A)Thermodynamic release(ambient temp+40 )Operation current of magnetic release(A)
1.0ln(cold state)
inoperative time(h)
1.20ln(heat state)
inoperative time(h)
1.50ln(heat state)
inoperative time(h)
1.0ln(heat state)
inoperative time(h)
12.5 ln 400224min2S Tp 10S12ln 20%

Specifications:
TypeRated current(A)Pole No.Rated insulating voltage (V)Rated operating voltageArcing over distance (mm)Ultimate short circuit breaking capacity(kA)Services short circuit breaking capacity(kA)Operation performance (Endurance)
ONOFF
NS-100D12.5, 16, 20, 25, 32, 40, 50, 63, 80, 1003
4
9506900181815008500
NS-100N2525
NS-100H7070
NS-100L150150
NS-160D16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160252510007000
NS-160N3636
NS-160H7070
NS-160L150150
NS-250D160, 180, 200, 225, 250252510007000
NS-250N3636
NS-250H7070
NS-250L150150
NS-400D200, 225, 250, 300, 315, 400353510004000
NS-400N1545
NS-400H7070
NS-400L150150
NS-630D315, 350, 400, 500, 600, 630353510004000
NS-630N4545
NS-630H7070
NS-630L150150

Contact us